Toshiba VF-nC1 User Manual

Page 72

Advertising
background image

E6581090

F-8

6

6.4

Analog signals for frequency setting

6.4.1 Setting frequency command characteristics

H : Analog input/logic input function selection

H : VI/S3 reference point 1 setting (%)

H : VI/S3 reference point 2 setting (%)

H : V1/S3 point 1 frequency (Hz)

H : V1/S3 point 2 frequency (Hz)

Function

By changing the setting of H, the function of the VI/S3 terminal can be switched
between 0~(5)10Vdc voltage input and 4~20mAdc current input.
The H to H parameters are used to adjust the output frequency according to the
analog signal (voltage: 0~(5)10Vdc, current: 4~20mAdc) from an external device.

Parameter setting

Title

Function

Adjustment range

Default setting

H

Analog input/logic input
function selection

0: Voltage signal input (0~10(5)Vdc)
1: Current signal input (0(4)~20Adc)
2: Contact input

0

H

VI/S3 reference point 1
setting (%)

0~100(%)

0

H

VI/S3 point 1 frequency (Hz) 0.0~200.0(Hz)

0.0

H

VI/S3 reference point 2
setting (%)

0~100(%)

100

H

VI/S3 point 2 frequency (Hz) 0.0~200.0(Hz)

*

Note 1: Do not specify the same value for input points 1 and 2. If you do so, the error message

“GTT” will be displayed.

* The value is changed according to the set-up parameter condition.

(VFNC1 (S)-□□□□P□-W type)
80 [Hz] for VFNC1 (S)-□□□□P□ type.

F (F: Forward run)

CC

S2(THR2)

R(AD2)

S1(MCHG)

Forward run command

Switching to motor 2

Switching to acceleration/deceleration 2

Switching to thermal 2