Motor 150%-overload time limit : H

Using the H parameter (motor 150%-overload withstanding time), you can set the time
(between 10 and 800 seconds) elapsed before an overload trip occurs (QN) when the motor is
operated under a load of 150%.

Title

Function

Adjustment range

Default setting

H

Motor 150%-overload time limit 10~800 (sec)

300

5.11

Preset speed operation (speeds in 15 steps)

UT UT : Preset speed operation frequencies 1~7 (Hz)
H

H : Preset speed operation frequencies 8~15

[Setting method]
1) Run/stop

The starting and stopping control is done from the terminal board.

Title

Function

Adjustment range

Default setting

Setting

EOQF

Command mode
selection

0: Terminal board
1: Operation panel

1

0

Note: If speed commands (analog signal or digital input) are switched in line with preset speed

operations, select the terminal board using the frequency setting mode selection HOQF.

⇒ See 3) or 5.1

2) Preset speed frequency setting

Set the speed (frequency) of the number of steps necessary.

Setting from speed 1 to speed 7

Title

Function

Adjustment range

Default setting

UT~UT

Preset speed operation
frequencies 1~7

NN~WN

(Hz)

0.0

Setting from speed 8 to speed 15

Title

Function

Adjustment range

Default setting

H~H Preset speed operation

frequencies 8~15

NN~WN

(Hz)

0.0

Example of a frequency setting for forward 15-speed operation

Examples of preset speed contact input signals: When the input terminals are placed in sink logic
mode

: ON - : OFF (Speed commands other than preset speed commands are valid when all are OFF)

Preset speed

Terminal

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

S1-CC

S2-CC

VI/S3-CC

R-CC

Terminal functions are as follows.

Terminal S1 ....................

Input terminal function selection 3 (S1) H=6 (SS1)

Terminal S2 ....................

Input terminal function selection 4 (S2) H=7 (SS2)

H

=2 (Contact input)

Terminal VI/S3................

Terminal VI and input terminal function
selection 5 (VI/S3)

H

=8 (SS3)

Terminal R......................

Input terminal function selection 2 (R)

H

=9 (SS4)

Function

A maximum of 15 speed steps can be selected just by switching an external contact signal.
Multi-speed frequencies can be programmed anywhere from the lower limit frequency NN
to the upper limit frequency WN.

S1

S2

VI/S3

R

CC