Jumping resonant frequencies – Toshiba VF-nC1 User Manual

Page 76

Advertising
background image

E6581090

F-12

6

6.7

Jump frequency –

Jumping resonant frequencies

H : Jump frequency (Hz)
H : Jump width (Hz)

Function

Resonance due to the natural frequency of the mechanical system operated can be avoided by
jumping the resonant frequency during operation. During jumping, hysteresis characteristics
with respect to the resonant frequency are given to the motor.

Jump width (H)

Jump frequency (H)

Output frequency [Hz]

Frequency setting signal

0

[Parameter setting]

Title

Function

Adjustment range

Setting

H

Jump frequency (Hz)

NN~WN

(Hz)

0.0

H

Jump width (Hz)

0.0~ 30.0 (Hz)

0.0

Do not set jump frequencies that overlap each other.

During acceleration or deceleration, the jumping function is disabled for the operation frequency.

6.8

Preset speed operation frequencies 8 to 15

H H : Preset speed operation frequencies 8 to 15 (Hz)

See Section 5.11 for details.

6.9

PWM carrier frequency

H : PWM carrier frequency

Function

1) This parameter is used for changing the carrier frequency in order to change the tone of the

magnetic noise produced by the motor. This parameter is also effective in preventing the
motor from resonating with its load machine or fan cover.

2) In addition, this parameter is used to reduce the electromagnetic noise produced by the

inverter. To reduce the electromagnetic noise, decrease the carrier frequency.
Note: This reduces the electromagnetic noise but increases the magnetic noise from the motor.

3) If the PWM carrier frequency is set above 4kHz, it may fall automatically during acceleration

or under certain circumstances where an overcurrent flows.

[Parameter setting]

Title

Function

Adjustment range

Setting

H

PWM carrier frequency

0:2kHz

1:2kHz(random control)

2:4kHz

3:4kHz(random control)

4:8kHz (automatic reduction mode) *1

5:12kHz(automatic reduction mode) *1

6:16kHz(automatic reduction mode) *1

5

*1 Cartain models require to reduce the rated load current according to carrier frequency setting

as following table.