Toshiba VF-nC1 User Manual

Page 109

Advertising
background image

E6581090

I-7

9

Table 4. AIC and fuse

Voltage class

Capacity of

applicable motor

(kW)

Inverter model

AIC

(Interrupting

capacity)

Fuse class and

currents(A)

0.1

VFNC1S-1001P

AIC 1000A

CC/J 6 max

0.2

VFNC1S-1002P

AIC 1000A

CC/J 8 max

0.4

VFNC1S-1004P

AIC 1000A

CC/J 12 max

Single-phase

100V class

0.75

VFNC1S-1007P

AIC 1000A

CC/J 22 max

0.2

VFNC1S-2002P(L)

AIC 1000A

CC/J 4 max

0.4

VFNC1S-2004P(L)

AIC 1000A

CC/J 8 max

0.75

VFNC1S-2007P(L)

AIC 1000A

CC/J 12 max

1.5

VFNC1S-2015P(L)

AIC 5000A

CC/J 22 max

Single-phase

200V class

2.2

VFNC1S-2022P(L)

AIC 5000A

CC/J 30 max

0.1

VFNC1-2001P

AIC 1000A

CC/J 3 max

0.2

VFNC1-2002P

AIC 1000A

CC/J 3 max

0.4

VFNC1-2004P

AIC 1000A

CC/J 5 max

0.75

VFNC1-2007P

AIC 1000A

CC/J 8 max

1.5

VFNC1-2015P

AIC 5000A

CC/J 15 max

Three-phase

200V class

2.2

VFNC1-2022P

AIC 5000A

CC/J 20 max

9.2.4 Motor thermal protection

Selects the electronic thermal protection characteristics that fit with the ratings and characteristics
of the motor. In case of multi motor operation with one inverter, thermal relay should be connected
to each motor.

Advertising