E6581090

F-29

6

Communications parameters (Common serial options)

The data transfer rate, parity type, inverter ID number and communication error trip time can be
changed from the operation panel or the computer on the network.

Title

Function

Adjustment range

Default setting

H

Communication baud rate

0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4:19200bps

3

H

Parity (Common serial)

0: Non (non parity)
1: Even (even parity)
2: Odd (odd parity)

1

H

Inverter number

0~99

0

H

Communication error trip
time

0: Disabled
1~100 (sec)

0

*: Disabled・・・Means that the inverter will not trip even if a communication error occurs.

Trip ・・・・・・・Means that the inverter will trip if a time-out occurs.
If a time-out occurs, the error message “GTT” will blink on the display panel.

6.16.1 Using RS232C/RS485 conversion units

Setting up the communications function

Commands (RUN/STOP commands) entered across a network have priority (over commands
from the operation panel or terminal boards).

Data transmission specifications

Item

Specifications

Data transmission
scheme

Half-duplex

Connection scheme

Centralized control

Synchronization
scheme

Asynchronous

Data transfer rate

Default: 9600 baud (parameter setting)
Selectable from among 1200, 2400, 4800, 9600 and 19200 baud

Character
transmission

ASCII mode ... JIS X 0201, 8-bit (fixed, ASCII)
Binary code ... Binary code, 8-bit (fixed)

Stop bit length

Receive (inverter): 1bit, Send (inverter): 2 bits

Error detection

Parity: Selectable among Even, Odd and Non by parameter setting,

Check sum method

Character
transmission format

Receiving: 11-bit, Sending: 12-bit

Order of bit
transmission

Lower-order bits first

Frame length

Variable to a maximum of 17 bytes

Examples of connection for RS485 communications
<Example of connection>

Optional unit

Host computer

nC1

nC1

nC1

nC1

nC1

・・・・

・・・・

Optional unit