Selection of wiring devices

Non-fuse circuit breaker (MCCB)

Earth leakage breaker (ELCB)

Magnetic contactor

(MC)

Overload relay

(THR)

Without reactor

With DC reactor

Without reactor

With DC reactor

Voltage

class

Capacity of

applicable

motor

(kW)

Inverter model

Rated
current

(A)

Type

MCCB /

(ELCB)

Note1)

Rated
current

(A)

Type

MCCB /

(ELCB)

Note1)

Rated
current

(A)

Type

Note1)

Rated
current

(A)

Type

Note1)

Adjusted

current

(A)

(For reference)

Type

Note1)

0.1

VFNC1S-1001P

5

---

---

9

---

---

0.7

LR3D056

0.2

VFNC1S-1002P

10

---

---

9

---

---

1.3

LR3D066

0.4

VFNC1S-1004P

15

---

---

9

LC1D096

---

---

2.3

LR3D076

Single-

phase

100V
class

0.75

VFNC1S-1007P

30

NJ30E

(NJV30E)

---

---

18

LC1D186

---

---

3.6

LR3D086

0.2

VFNC1S-2002P(L)

5

5

9

9

1.3

LR3D066

0.4

VFNC1S-2004P(L)

10

5

9

9

2.3

LR3D076

0.75

VFNC1S-2007P(L)

15

10

9

LC1D096

9

LC1D096

3.6

LR3D086

1.5

VFNC1S-2015P(L)

20

15

18

LC1D186

12

LC1D126

6.8

LR3D126

Single-

phase

200V
class

2.2

VFNC1S-2022P(L)

30

NJ30E

(NJV30E)

30

NJ30E

(NJV30E)

25

LC1D256

18

LC1D186

9.3

LR3D146

0.1

VFNC1-2001P

5

5

9

9

0.7

LR3D056

0.2

VFNC1-2002P

5

5

9

9

1.3

LR3D066

0.4

VFNC1-2004P

5

5

9

9

2.3

LR3D076

0.75

VFNC1-2007P

10

5

9

9

3.6

LR3D086

1.5

VFNC1-2015P

15

10

9

LC1D096

9

LC1D096

6.8

LR3D126

Three-

phase

200V
class

2.2

VFNC1-2022P

20

NJ30E

(NJV30E)

15

NJ30E

(NJV30E)

12

LC1D126

12

LC1D126

9.3

LR3D146

Note 1: Produced by Toshiba Schneider Electric Ltd.
Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor.

Selection of surge killers for Toshiba magnetic contactors
200V class: Surge absorbing units are optionally available for Toshiba C11J to C20J

Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the

contacts 2a in parallel to increase reliability.

Of the wiring devices listed in the above table, the magnetic contactors (MC) and the overload relays (Th-Ry)
are intended for use with the Mighty J series. When using the old series (ESPER Mighty series), refer to the
table below showing the correspondence between the two series.

Magnetic contactor (MC)

Overload relay

ESPER Mighty series

Mighty J series

ESPER Mighty series

Mighty J series

C12A

C13J

T11A

T13J

C20A

C20J