Error
code

Alarm

code

Problem

Possible causes

Remedies

*
GRJ

0008

Input phase failure

• A phase failure occurred in the

input line of the main circuit.

• The inverter may trip because of

GRJ

if switching between

acceleration and deceleration is
done in succession at intervals
of less than 1 second.

• Check the main circuit input line

for phase failure.

• Enable H (input phase

failure detection). Set the
H

parameter to 0.

QJ

0010

Overheat

• The cooling fan does not rotate.
• The ambient temperature is too

high.

• The vent is blocked up.
• A heat generating device is

installed close to the inverter.

• The thermistor in the unit is

broken.

• Restart the operation by

resetting the inverter after it has
cooled down enough.

• The fan requires replacement if

it does not rotate during
operation.

• Secure sufficient space around

the inverter.

• Do not place any heat-

generating device near the
inverter.

• Make a service call.

*WR

001E

Undervoltage trip
(main circuit)

• The input voltage (in the main

circuit) is too low.

• Check the input voltage.
• Enable H (undervoltage

trip selection).

• To cope with a momentary stop

due to undervoltage, enable
H

(ride-through control)

and H (auto-restart).

GH

0022

Ground fault trip
Arm overcurrent

• A ground fault occurs in the

output cable or the motor.

• A main circuit element is

defective.

• Check the cable and the motor

for ground faults.

• Make a service call.

G

0011

Emergency stop

• During automatic operation or

remote operation, a stop
command is entered from the
operation panel or a remote
input device.

• Reset the inverter.

GTT

0015

Main unit RAM fault

• The control RAM is defective.

• Make a service call.

GTT

0016

Main unit ROM fault

• The control ROM is defective.

• Make a service call.

GTT

0017

CPU fault trip

• The control CPU is defective.

• Make a service call.

GTT

0018

Remote control
error

• An error arises during remote

operation.

• Check the remote control

device, cables, etc.

GTT

001A

Current defector
fault

•The current detector is defective. • Make a service call.

GGR

0012

EEPROM fault 1

• A data writing error occurs.

• Turn off the inverter, then turn it

on again. If it does not recover
from the error, make a service
call.

GGR

0013

EEPROM fault 2

• Power supply is cut off during

V[R

operation and data

writing is aborted.

• Turn the power off temporarily

and turn it back on, and then try
V[R

operation again.

GGR

0014

EEPROM fault 3

• A data writing error occurs.

• Turn off the inverter, then turn it

on again. If it does not recover
from the error, make a service
call.

*
G

0032

Break in analog
signal cable

• The signal input via VI/S3 is

below the analog signal
detection level set with H.

• Check the cables for breaks

and change the setting of
H

if no breaks are found.

(Continued overleaf)