Entellisys Low Voltage Switchgear

Chapter 3. Description

Fuses for the charge, close, and trip circuits of electrically

operated breakers are mounted in the upper left corner of the

breaker compartment behind the door. Fuses for the set and

reset coils of the optional Network Interlock breaker

accessory are mounted in the upper right corner of the

compartment.

Primary disconnect shutters are available as options to

provide protection against contact with the energized

stationary primary disconnects when the breaker is removed

from its compartment. Shutters are supplied as standard

components in the source (main, generator) and tie breaker

compartments of multi-source lineups. The shutters are

constructed from glass-reinforced polyester insulating

material.

NOTE: If a fuse rollout (FRE) carriage is used with an

EGF-32/40/50 circuit breaker whose compartment is

equipped with shutters, the FRE compartment will also be

equipped with shutters.

NOTE: Si on utilise un chariot porte-fusibles à roulettes

avec un disjoncteur EGS-32/40/50 dont les compartiments

sont munis de volets, le compartiment du porte-fusible à

roulettes sera aussimuni de volets.

The combination of the stationary and movable portions of

the shutters prevent frontal access to the primary disconnect

line and load power stabs.



Fig. 3-6. Circuit breaker compartment (30-inch wide) with shutters











1. Stationary barrier
2. Shutters (retractable barrier)
3. Operating lever
4. Operating lever springs
5. Drawout rails
6. Racking anchor pins