1 maintenance requirements, 2 breaker and instrument compartments, General – GE Industrial Solutions Entellisys Installation User Manual

Page 67: Breakers, Checks after breaker is de-energized

Advertising
background image

61

Entellisys Low Voltage Switchgear

Chapter 9. Maintaining the Switchgear

9-1 Maintenance Requirements

General

A periodic maintenance schedule must be established to

obtain the best service from the switchgear. Under the

conditions of a clean and dry environment, a check of the

switchgear devices and all connections should be made once

every two years. Equipment subject to highly repetitive

operation or to a dusty or humid environment may require

more frequent maintenance.

A permanent record of all maintenance work should be kept.

The record should include a list of periodic checks and tests

made, the date they were made, the condition of the

equipment, and any repairs or adjustments that were

performed. Maintenance employees must follow all

recognized safety practices, such as those contained in the

National Electric Safety Code, ANSI C2-1981 and in company

or other safety regulations.

WARNING: Solid insulation surrounding an energized

conductor and power apparatus must never be relied upon

to provide protection to personnel.

ADVERTISSEMENT: Il ne faut pas se fier à une isolation

solide entourant un conducteur mis sous tension et à la

puissance de l’appareillage pour fournir une protection aux

membres du personnel.

For specific information regarding the maintenance of circuit

breakers and Entellisys instrumentation, refer to the

instruction book furnished with each device.

9-2 Breaker and Instrument
Compartments

Periodic inspection of the circuit breaker is recommended at

least once a year. More frequent inspections are

recommended where severe load conditions, dust, moisture or

other unfavorable conditions exist, or if the vital nature of

the load warrants it. Always inspect the breaker after a

short-circuit current has been interrupted.

Breakers

Test for Proper Operation
Test and inspect all circuit breakers for proper operation as

follows:

1.

Operate each breaker while in the TEST position and

check all functions. This is particularly important for

breakers that normally remain in either the opened or

closed positions for long periods of time.

WARNING: Primary equipment must be completely de-

energized while tests on control circuits, etc. are being

conducted. Be sure that all areas of feedback from

secondary circuits, as well as outside sources, are

disconnected.

ADVERTISSEMENT: Il faut que l’équipement primaire

soit complètement désamorcé lorsque des tests sont

effectués sur des circuits de contrôle, etc. Assurez-vous que

toutes les aires de rétroaction des circuits secondaires de

même que les sources extérieures soient débranchées.


2.

Remove the breakers from their compartments to a

clean maintenance area. Close compartment door and

cover the breaker cutout to prevent access to live parts.

WARNING: De-energize equipment completely before

doing maintenance work on any devices, connections, bus

work, breaker or feeder cable compartments. This includes

de-energizing any connections to outside primary or

secondary sources, such as transformers, tie lines, etc.

ADVERTISSEMENT:

Désamorcer complètement

l’équipement avant d’effectuer du travail de maintenance

dans les compartiments. Cela inclut le désamorçage de

toute connexion aux sources primaires et secondaires,

telles que les transformateurs et les interconnexions.

Checks After Breaker Is De-energized

At the time of inspection, the following checks should be

made after the breaker has been de-energized.

1.

Manually operate the breaker several times, checking

for obstructions or excessive friction. Manual closing of

an electrically operated breaker may be performed by

the following two steps:

a.

For the EG-32/40/50 frame breakers, raise the

breaker frame off the work surface to ensure the

spring discharge interlock is not depressed. To

charge the mechanism springs, pull the operating

handle down until it stops (about 90°) five-six times

for the EG-08/16/20 and eight times for the EG-

32/40/50 frame. The charge indicator will show

CHARGED on a yellow background.

b.

Depress the CLOSE button on the front of the

breaker. The springs should discharge and, if the

latch is properly reset, the breaker will close.

2.

Electrically operate the breaker several times to check

performance of the electrical accessories.

3.

Visually check for loose hardware on the breaker. Also,

check the bottom of the compartment for any hardware

that has fallen from the breaker.

4.

Remove and inspect the arc quenchers and contacts for

breakage or excessive burning.


5.

Check insulating parts for evidence of overheating and

for cracks that indicate excessive thermal aging.

Refer to circuit breaker instruction manuals for detailed

maintenance instructions and information for replacement of

parts. See DEH-203, DEH-204, DEF-004 or DEF-005.

Advertising