Entellisys Low Voltage Switchgear

Chapter 3. Description

Fig. 3-19 illustrates the various components comprising the

insulation/isolation system for the horizontal main bus bars.

The horizontal bus bars (2) are insulated with an epoxy

coating applied by a fluidized bed process. The vertical/

horizontal bus bar joints are covered with collars (3) and caps

(4) held in place with nylon thumb screws (5). The collars

and caps are constructed from insulating material.


1. Vertical bus barrier

2. Insulated bus bar (powder coated)

3. Joint collars

4. Joint caps

5. Nylon thumbscrews

Fig. 3-19. Horizontal bus insulation system





















3-11 Feeder Cable and Busway
Compartment

The rear cable and terminal compartment, Fig. 3-20, provides

for cable installation and terminations. The cable bending

space meets the requirements of the 2005 National Electric

Code. Various arrangements of single or double cable

terminals are provided, depending upon the purchaser's

requirements.




1. Support rack for customer's feeder cables

2. Cable lugs - mechanical type

3. Cable lugs - compression type


Fig. 3-20. Cable termination provisions


When specified, racks (1), Fig. 3-20, for the support of feeder

cables are located in the cable compartment. The actual

support of the cables is provided by lashing them to these

racks.

A neutral bus, insulated from ground, is provided in the bus

area on switchgear designed for four-wire systems. The

neutral bus is located near the top of the cable compartment.

It includes provisions for terminating the neutral conductor

of four-wire feeder cables and also direct mounting of the

neutral CT as required for those feeder system circuit

breakers having an integral ground fault trip function.