GE Industrial Solutions Entellisys Installation User Manual

Page 31

Advertising
background image

25

Entellisys Low Voltage Switchgear

Chapter 4. Equipment Installation

NOTE: When the equipment is installed on a surface

subject to impact (shock) loads due to operating

conditions or environmental seismic (earthquake)

conditions, the anchor bolts should be fabricated of

medium carbon steel (grade 5 load rating).

NOTE: Lorsque l’équipement est installé sur une surface

sujette à des charges d’impact (choc) causées par les

conditions d’opération ou des séismes environnementaux

(tremblements de terre), les boulons d’ancrage devraient

être fabriqués d’acier à moyenne teneur en carbone

(spécification de charge classe 5).

The floor channels under the front and rear switchgear

anchor points (see Fig. 4-2) should be embedded in a level

concrete slab with their top surfaces flush with the finished

floor. It is essential that these steel channels be level and

aligned with each other prior to final anchoring, to prevent

distortion of the switchgear structure, to assure proper

mechanical and electrical connections between shipping

splits, and to assure proper interfacing to other close-coupled

equipments.

Entellisys Switchgear and Load Center Substations are

frequently mounted on steel floors and/or structural steel in

industrial installations (such as a mezzanine) to minimize

usage of production floor space. Regardless of the type of

mounting surface, the requirements for a smooth level

surface remain.

Fig 4-2. Location of equipment anchor points

Advertising