Entellisys Low Voltage Switchgear

Chapter 7. Operating the Switchgear

Care must be exercised when installing or removing phase

current transformer mounting screws so as not to strip the

holes in the plastic base. Do not torque screws over five

in/lbs.

Removing Shutter Units

Visual inspection of primary disconnects and CT's can be

made by first removing the breaker and opening the

shutters manually. This is done by pressing the left and

right hand actuating rollers toward the rear of the

compartment simultaneously. This is a two-handed

operation.

If it is necessary to perform work on the primary

disconnects or CT’s, it will be necessary to remove the

entire shutter unit.

WARNING: Unless the proper precautions are taken,

the removal of a shutter unit presents the hazard of

electrical shock and burn. Do not remove the shutter

unit unless the equipment has been de-energized.

Failure to do this can result in serious injury.

ADVERTISSEMENT

:

A moins que les précautions

nécessaires ne soient prises, l’installation d’une unité à

volet présente des risques de choc électrique ou de

brûlure. Il ne faut pas installer l’unité à volet à moins

que l’équipement ait été désamorcé. L’omission de ce

faire peut résulter en blessures sérieuses.



1. Frame assembly

7. Support block

13. Spring

2. Frame assembly

8. Support block

14. Complete upper shield

3. Shutter Actuator

9. Bottom shield

assembly

4. Bottom shutter

10. Connector link

15. Shield cover

5. Support Block

11. Spring

16. Label

6. Center shield

12. Spring

Fig. 7-9. Entellisys circuit breaker shutter unit (EGS-08/16 breakers)