Entellisys Low Voltage Switchgear

Chapter 3. Description

A vertical barrier (2),

Fig.

3-17, between the transition

section (1) and the first breaker section is always

furnished.

The buswork in the device/auxiliary/transition sections is

not insulated at the termination points to the other

connected equipments such as transformers, busway, or

existing equipments.


1. Transition compartment

2. Barrier

3. Main incoming bus

4. Neutral bus

5. Ground bus

Fig. 3-17. Transition section


Insulation and isolation of the vertical riser bus bars (2),

Fig. 3-18, is provided by installing phase isolation barriers

(3) between the bus bars and by mounting covers (4) over

the bus bars. (The top portion of the vertical bus is shown

with the cover removed.)


The phase isolation barriers and riser bus covers are

constructed from insulating material. Insulation of the

horizontal main bus bars (5) is achieved by an oven cured

coating of epoxy.




1. Molded base
2. Vertical riser buses (cover removed to show bus

location)

3. Phase isolation barriers
4. Covers over riser bus
5. Insulated horizontal main buses
6. Covers for vertical/horizontal bus joints
7. Insulated run backs

Fig. 3-18. Bus insulation system