GE Industrial Solutions Entellisys Installation User Manual

Page 37

Advertising
background image

31

Entellisys Low Voltage Switchgear

Chapter 4. Equipment Installation

All bolted bus joints should be made using the proper torque

as shown in Table A-1 in Appendix A of this manual.

Transformers not manufactured by General Electric may

require special mounting and bus connection hardware.

The neutral bus may be insulated from the grounded frame of

the switchgear equipment; thus, it is mounted on insulators

throughout the equipment. Installation of the neutral bus

splice plate across a shipping split is similar to the ground

bar splice except that the splice plate is not bolted to the

equipment frame. Fig. 4-11 illustrates the installation of the

neutral splice plate.

Fig. 4-11. Plan view of neutral bus splice installation

The installation of the horizontal bus splice bars is with

bolted joints.

Figs. 4-12 and 4-13 illustrate the assembly of the main bus

splice plates on the bolted bus system. Copper bus systems

are normally supplied with flat washers and lock washers.

Fig. 4-12 shows the rear view of the main bus area with the

installed splice bus indicated with cross-hatching.

Fig. 4-13 shows that a spacer is used both between the

busbars when more than one bar is used per phase (normally

the 2500 ampere and larger main bus ratings) and over the

outer bars of a single or multiple bar joint.

After assembly of the splice plates and spacers, the 1/2-13

bolts should be tightened to a torque of 35-40 ft-lbs.



Fig. 4-12. Rear view of main bus at a shipping split

Fig. 4-13. Plan view of a two bar main bus connection


Advertising