58

Entellisys Low Voltage Switchgear

Chapter 7. Operating the Switchgear




1. Side frame assembly (right)

4. Front shield

2. Side frame assembly (left)

5. Shutters

3. Movable shield assembly

6. Shutter actuator

Fig. 7-10. Entellisys circuit breaker shutter unit (EG-32/40/50 breakers)


Removing an EG-08/16/20-Shutter Unit

To remove these shutter units, proceed as follows:

1.

The shutter unit frame is mounted on the vertical

stringers located at each side of the rear of the breaker

compartment. See Fig. 7-9. In extended

compartments, the shutter is mounted to extension

brackets.


2.

If it is present, remove the Clamp Circuit, mounted on

the left hand side sheet. Remove the twelve wires from

the two terminal blocks, and then remove the ¼-inch

hex head screws from the enclosure.

3.

Take out two 1/4-inch hex head screws on each side of

the frame. A socket wrench with a 3/8-inch driving

head with 4-inch extension will be needed.

4.

Carefully remove the entire shutter frame.

5.

The frame is then maneuvered forward past the cam

plates on each side, then upward and forward over the

cam pins.

Removing an EG-32/40/50 or Fuse Roll Out

Shutter Unit

To remove these shutter units, proceed as follows:

1.

The shutter unit frame is mounted to the vertical

stringers located at each side of the rear of the breaker

compartment. See Fig. 7-10.


2.

Take out 11 ¼-inch hex head screws from the frame. A

socket wrench with a 3/8-inch driving head with an 8-

inch extension will be needed. See Fig. 7-10.

3.

Carefully remove the entire shutter frame.