Entellisys Low Voltage Switchgear

Appendix B. Circuit Breaker Rejection Features


General

In general, EntelliGuard breakers of the same type and

rating are interchangeable in their equipment compartments.

Similarly, breakers may be installed into equipment

compartments designed for breakers having lower ratings.

Breakers are intentionally made uninstallable into

compartments for breakers with higher ratings.. To prevent

inserting the wrong type breaker into a drawout

compartment, unique “rejection hardware” is affixed to each

breaker and its compartment. The rejection is accomplished

by tabs or pins on the bottom of the breaker backframe and

tabs or pins on the top of the pan in the equipment

compartment.

Fig. B-1. Breaker-mounted rejection plate






22-inch Wide Compartment

Figure B-1 (EG-08/16/20 breaker family) shows the breaker-

mounted rejection tabs located on the bottom left side of the

backframe.

When a wrong type breaker is inserted into a compartment,

the breaker tabs and equipment pins interfere, preventing

the breaker from rolling into the DISCONNECT position.

Breakers may be interchanged in one direction only.

Specifically:

1. Any EG-08/16/20 breaker can be inserted into an

EGS-08 compartment.

2. An EGX-08, EGH-16, EGS-20 or EGF-20 can be

inserted into an EGH-08 compartment.

3. An EGS-20 or EGF-20 may be inserted into an EGX-

08 or EGH-16 compartment

4. An EGH-16, EGS-20, or EGF-20 may be inserted

into an EGS-16 compartment

5. An EGF-20 may be inserted in an EGS-20

compartment

The rejection hardware prevents the converse of the above.

Figure B-2 shows the rejection pin combinations employed for

the various breaker models and frame sizes.