Entellisys Low Voltage Switchgear

Chapter 3. Description

Movement of the breaker between the CONNECTED, TEST,

and DISCONNECTED positions is performed by the use of a

racking crank that engages the racking mechanism mounted

on the breaker. Movement to the WITHDRAWN position is

manually performed after opening the compartment door.

These positions are illustrated and described more fully in

Chapter 5 of this instruction book.


CAUTION: The door should not be opened when the circuit

breaker is closed and in the CONNECTED position.

Although the breaker compartment door may be opened in

any position, it is recommended that the door only be

opened when the breaker is in the DISCONNECTED or

WITHDRAWN position.

ATTENTION: Il ne faut pas que la porte soit ouverte

lorsque le disjoncteur est fermé et branché. Bien que la

porte du compartiment du disjoncteur puisse être ouverte

lorsque le disjoncteur est en n’importe quelle position, il

est préférable que la porte ne soit ouverte que lorsque le

disjoncteur est en position débranchée ou retirée.


3-6 Circuit Breakers

The General Electric EntelliGuard

Low Voltage Power

Circuit Breaker includes spring-operated, stored energy, close

and trip mechanisms for either manual or electrical

operation.


Six General Electric EntelliGuard

Circuit Breakers form

the complete family of breakers used in the Entellisys

switchgear. These circuit breakers range from 800 to 5000

ampere frame sizes and are built with the following ratings

and characteristics:

EGS/EGH/EGX-08 Circuit Breaker

• 800-ampere frame size

• Standard 30,000-ampere interrupting and short-time

capability (480 volts)

• Four-high stacking, 22-inch wide sections

• Increased IC and short-time rating 42,000 amperes

(EGH-08) or 65,000 amperes (EGX-08) at 480 volts

EGF-08 Fused Circuit Breaker

• 800-ampere frame size

• 300- through 1600-ampere integral fusing

• 200,000-ampere interrupting rating

• Four-high stacking, 22-inch wide sections

EGS/EGH-16 Circuit Breaker

• 1600-ampere frame size

• Standard 50,000-ampere interrupting and short-time

capability at 480 volts

• Four-high stacking, 22-inch wide sections

• Increased IC and short time rating 65,000-ampere at 480

volts (EGH-16)




Fig. 3-10. EGX-08 circuit breaker (electrically operated)

EGF-16 Fused Circuit Breaker

• 1600-ampere frame size

• 450- through 2500-ampere integral fusing

• 200,000-ampere interrupting rating

• Four-high stacking, 22-inch wide sections

EGS/EGF-20 Circuit Breaker

• 2000-ampere frame size

• Standard 65,000-ampere interrupting and short-time

capability at 480 volts

• 200,000-ampere interrupting rating

• Three-high stacking, 22-inch wide sections (See DET-

447)