39

Entellisys Low Voltage Switchgear

Chapter 4. Equipment Installation


4-3 Installation of Wall-Mount HMI


General Requirements

Before installation, ensure the surface to which the enclosure will
be mounted is capable of safely supporting 85 lb.

Fig. 4-25. Wall-mount HMI enclosure

Enclosure Installation

The recommended procedure for installation of a wall-mount

HMI is as follows:

1. Add a conduit connection hole in either the top or

bottom wall of the enclosure. Do not position the hole

less than 1.5 inches from the edges of the enclosure.

See Fig. 4-28 for area suitable for conduit hole.

2. Four mounting holes are provided in the back of the

enclosure. Drill an identically spaced pattern of holes

in the surface to which the enclosure will be mounted

according to the drawing supplied with the enclosure.

3. Attach the enclosure to the wall or other structure

using 3/8 inch bolts, flat washers, and, if the bolts are

not self-threading, lock washers and nuts. To ensure

proper sealing and enclosure protection rating, use

the provided sealing washers. Install the sealing

washers inside the enclosure with the tapered cone

against the enclosure and then add the flat washers

as shown in Figs. 4-26 and 4-27.

4. Attach a suitable conduit fitting to the hole from

Step 1. Run conduit to the enclosure as necessary.

Fig. 4-26. Mounting the enclosure with bolts and nuts

Fig. 4-27. Mounting the enclosure with self-threading bolts

Device Wiring

The recommended procedure for connecting the HMI power

and communication cables is as follows:

1. Connect 120VAC line, neutral, and ground wires to

terminal block as shown in the wiring diagram

included with the assembly.

2. Connect incoming Ethernet cable to the port on the

side of the HMI. Secure the wires to HMI and

enclosure with cable ties.

3. If the enclosure is equipped with a power supply and

RS232/RS485 converter, connect the incoming

RS485 cable to converter terminals RX+ and RX-.