8 compartments for future breakers – GE Industrial Solutions Entellisys Installation User Manual

Page 24

Advertising
background image

18

Entellisys Low Voltage Switchgear

Chapter 3. Description



1. Quarter-turn latch
2. Steel plate (future breaker cubicle)


3. Compartment door

Fig. 3-13. Future breaker compartment

3-8 Compartments for Future
Breakers

When specified, compartments may be supplied for future

addition of circuit breaker elements. These compartments

are fully equipped with drawout rails, primary

disconnects, and ancillary devices as required (i.e.

secondary disconnects, accessory devices, etc.) The
opening in the breaker compartment door (3),

Fig.

3-13, is

closed with a bolted-on steel plate (2) to deter accidental

contact with energized electrical circuits. (I.e. primary

disconnect stabs).











3-9 Auxiliary/Transition Sections

Sections may be provided for any one or more of several

reasons including:

• Transition to a close-coupled transformer

• Incoming cable or busway when a main breaker

section is not provided

Auxiliary sections may be 22-inch, 30-inch, or 38-inch

wide as required to accommodate the space requirements.

The compartment doors on the front of the sections are

hinged and latched in the same manner as breaker

compartment doors.

Generally, transition sections will be 22-inches wide for

close-coupling to transformers.

Power company metering requirements generally require

either a 38-inch or 49-inch wide auxiliary section to

accommodate the current transformers, meters, test

switches, etc. as required by their individual practices,

tariff schedules, and/or regulatory commissions.




3

2

1

Advertising