Entellisys Low Voltage Switchgear

Appendix E. Circuit Breaker Weights

Net Weight, lb. (kg)

Device

Manual

Electrical

EGS/EGH/EGX-08

EGF-08

EGS/EGH-16

EGF-16

EGS-20

EG-32
EG-40
EG-50

188 (86)

233 (106)

198 (90)

243 (111)

203 (92)

455 (207)
560 (255)
600 (273)

193 (88)

238 (108)

203 (92)

248 (113)

208 (95)

470 (214)
575 (261)
615 (280)

2000 Ampere

Fuse Rollout

250 (114)

-

3200-Ampere

Fuse Rollout

350 (159)

-

4000-Ampere

Fuse Rollout

400 (182)

-

5000-Ampere

Fuse Rollout

450 (205)

-

Table E-1. Circuit Breaker/Fuse Rollout Element Weights


Appendix F. Circuit Breaker Repetitive Duty Data

General

Circuit breakers are designed primarily to perform the

function of circuit interruption under short-circuit conditions.

Nevertheless modern circuit breaker mechanisms are capable

of many operations under full-load operation and in-rush

conditions such as encountered in motor starting

applications. Industry standards have been established for

the minimum performance that is indicated in Table F-1.

With adequate maintenance, GE breakers can be expected to

exceed the standards.


Circuit Breaker

Frame Size

(Amperes)

Number of

Operations

Between

Servicing

Number of

Operations

Rated Continuous

Current

Switching*

(1) (2) (3) (4) (5)

(6) (7) (8) and (10)

Number of

Operations

No-Load

Closing and

Opening*

(1) (2) (3) (4)

(5) (6) and (7)

Number of

Operations

In-Rush
Current

Switching*

(3) (4) (5) (6))

(7) (9) and (10)

800

1600

1750

500

2800

800

9700
3200

1400

400

2000
3000
4000
5000

500
250
250
250

800
400
400
400

3200
1100
1100
1100

400



*Refer to lettered paragraphs under NOTES.

Table F-1. Repetitive Duty and Normal Maintenance

Notes

Power operated circuit breakers, when operating under usual

service conditions, shall be capable of operating the number

of times specified in Table F-1. The operating conditions and

the permissible effect of such operations upon the breaker are

given in the following lettered paragraphs. For each column,

all paragraphs listed in the column heading must be given

consideration.