1 circuit breaker operation, 2 circuit breaker drawout operation – GE Industrial Solutions Entellisys Installation User Manual

Page 59

Advertising
background image

53

Entellisys Low Voltage Switchgear

Chapter 7. Operating the Switchgear

7-1 Circuit Breaker Operation

General

Included below are abbreviated operating instructions for

EntelliGuard circuit breakers. Before activation of the circuit

breakers or operation of the switchgear equipment,

thoroughly read, and be familiar with, the circuit breaker

manuals that will be supplied as supplementary information

to this manual. Publication numbers are: DEH-201 and

DEH-202.

Manually Operated Breakers

Closing Manually Operated EntelliGuard Circuit

Breakers

Manually operated EntelliGuard breakers are equipped with

an integral charging handle and a push button marked

CLOSE on the front of the escutcheon. The spring must be

charged first.

1.

FOR EG-08/16/20 BREAKERS - A complete charge is

accomplished by pulling the handle down about 90°

(until it stops) five-six times to fully charge the closing

springs. This will not close the breaker contacts. The

charge indicator will show CHARGED on a yellow

background.


2.

FOR EG-32/40/50 BREAKERS - These breakers require

the handle to be pulled down eight times to fully charge

the springs. The charge indicator will show CHARGED

on a yellow background.

Opening Manually Operated EntelliGuard Breakers

A mechanically operated, double insulated open button,

mounted on the breaker escutcheon, operates the trip shaft to

open the breaker. The breaker many also be opened by the

Entellisys HMI.

Electrically Operated Breakers

The breakers may be closed by a mechanically operated, double
insulated push-button switch on the breaker escutcheon or by the
Entellisys HMI. Fuses are located in the breaker compartment,
just behind the door.

Electrically Opening EntelliGuard Breakers

Electrically operated EntelliGuard breakers are equipped with
both a shunt trip and a flux shifter for opening the breaker. A
normally open auxiliary switch “A” contact opens the shunt trip
control circuit after the breaker opens, preventing damage to the
device. The shunt trip and flux shifter operate in response to
OPEN and TRIP commands, respectively, from the HMI
breaker control screen.






7-2 Circuit Breaker Drawout
Operation

Breaker Positions

Refer to Fig. 7-1. The drawout operation features four

positions:

1.

CONNECT - In the CONNECT position, the primary

and secondary disconnects are fully engaged. The

breaker must be opened before it can be racked out of

this position.


2.

TEST - When in the TEST position, the primary

contacts are disconnected, but the secondary contacts

remain engaged. This allows complete breaker

operation without energizing the primary circuit.


3.

DISCONNECT - In the DISCONNECT position, neither

primary or secondary contacts are made. Breakers may

be racked between these three positions with the

compartment door closed and latched.


4.

WITHDRAWN - With the door open, the breaker can be

rolled out manually from the DISCONNECT to the

WITHDRAWN position. Here, the breaker is

completely out of its compartment, ready for removal.


Fig. 7-1. EntelliGuard circuit breaker

Shown in DISCONNECT position

Advertising