54

Entellisys Low Voltage Switchgear

Chapter 7. Operating the Switchgear


Drawout Operation

All breakers are supported on the drawout rails mounted on

the sidewalls of the breaker compartments. On EntelliGuard

breakers, two wheels on each side of the breaker rest on each

drawout rail.

Motion is provided by a mechanism mounted on the breaker.

This mechanism drives racking cams that engage pins

anchored to each side of the compartment.

The cams are driven by a removable racking handle that

engages the mechanism. On small frame breakers, the

handle is inserted through an opening in the breaker

escutcheon; on large frame breakers, the handle is inserted in

an opening in the upper right side of the door.

Turning the handle in a clockwise direction drives the

breaker into the compartment. As the breaker disconnect

fingers engage the stationary studs, a high force will be felt.

Turn the racking handle as far as it will go to be sure the

disconnect fingers are completely engaged.

The position indicator in the breaker escutcheon gives the

position of the breaker as it moves through the door cutout.

7-3 Front Doors

Operation

The front access doors on all standard Entellisys Switchgear

are hinged and equipped with a ¼-turn latch, Fig. 7-3. To

open the door, rotate the knob clockwise ¼ turn.

Removal and Installation

Refer to Fig. 7-3 and remove/install switchgear front doors.

Door Removal

To remove the Entellisys Switchgear door, proceed as follows:

1.

Open door.

2.

Loosen the two screws holding the top hinge pin plate

and allow the pin to drop out of the hinge block. See Fig.

7-3.

3.

Move the top of the door away from the switchgear,

avoiding the door stop and lift the door out of the lower

hinge pin socket. Retain the washer from the bottom

hinge pin.

Door Installation

To install the Entellisys Switchgear door, proceed as follows:

1.

Insert washer, then place lower hinge pin into hinge pin

socket on switchgear. See Fig. 7-3.

2.

Swing door open, position behind door stop and align

hinge pin socket.

3.

Insert the hinge pin into the upper hinge block and

tighten the two screws.

4.

Close the door.

Fig. 7-2. Entellisys switchgear front access doors are hinged with a

rotary-type latch

Fig. 7-3. Drawing showing front access details