7 fuse rollout elements – GE Industrial Solutions Entellisys Installation User Manual

Page 23

Advertising
background image

17

Entellisys Low Voltage Switchgear

Chapter 3. Description

EGS/EGH/EGX/EGF -32 Circuit Breaker

• 3200-ampere frame size

• Standard 65,000-ampere interrupting and short-time

capability at 480 volts

• 30-inch wide sections, Two-high stacking in 38-inch wide

sections

• Increased IC and short-time rating 85,000 amperes

(EGH-32) or 100,000 amperes (EGX-32) at 480 volts.

EGS/EGX/EGF -40 Circuit Breaker

• 4000-ampere frame size

• Standard 85,000-ampere interrupting and short-time

capability at 480 volts

• 30-inch wide sections, Two-high stacking in 38-inch wide

sections

• Increased IC and short-time rating 100,000 amperes

(EGX-40) at 480 volts.

Fig. 3-11. EGS-32 circuit breaker (electrically operated)

EGS/EGX/EGF -50 Circuit Breaker

• 5000-ampere frame size, fan cooled

• Standard 85,000-ampere interrupting and short-time

capability at 480 volts

• One-high stacking, 38-inch wide sections

• Increased IC and short-time rating 100,000 amperes

(EGX-50) at 480 volts.”

3-7 Fuse Rollout Elements

When the system available short-circuit current exceeds the

unfused breaker ratings, current-limiting fuses can be used

in series with EGF-20, EGF-32, EGF-40, and EGF-50

breakers to increase the short-circuit rating of the

combination to 200,000 amps. When used, such fuses are

housed in a separate drawout compartment located adjacent

to the breaker compartment; they are mounted on a drawout

carriage similar to a breaker frame and referred to as a fuse

rollout element (FRE).



EGF-32 Rollout Carriage

• 3200-ampere rating

• 200,000-ampere interrupting rating

• Accepts 2000- through 4000-ampere fusing

• Also used for EGF-20 breaker

EGF-40 Rollout Carriage

• 4000-ampere frame size

• 200,000-ampere interrupting rating

• Accepts 2000- through 5000-ampere fusing

EGF-50 Rollout Carriage

• 5000-ampere frame size

• 200,000-ampere interrupting rating

• Accepts 2000- through 5000-ampere fusing



1. Protective hinged screen

2. Racking mechanism

3. Fuses

4. Secondary disconnects

Fig. 3-12. Fuse roll-out carriage