Entellisys Low Voltage Switchgear

Chapter 4. Equipment Installation


Power Cable Connections

Connect the main cables to the main lugs. Before any

main cable connections are made, the cables should be

identified to indicate their phase relationship with the

equipment. Adequate electrical and mechanical

clearances must be provided between conduit, cables, and

bus. Where the cables enter the section, they can be

lashed to optional cable supports at the rear of the cable

compartment as required. (See Fig. 3-20.)

Mechanical cable terminals are normally included with

the switchgear (compression terminals are supplied when

ordered) and are mounted at the ends of the breaker

runbacks in the cable compartment. Carefully follow the

cable manufacturer's recommendations for installation of

cable.

Install the cables in the proper path to the terminals,

using temporary lashing if required. Cut the cables to the

proper length. Strip the insulation to the desired

dimension, being careful not to damage any strands.

For copper cables, coat the wires with GE lubricating

grease D6A15A2, insert the cables into the terminals, and

tighten the set screws in accordance with torque values

shown in the torque value table for cable terminals in the

addendum of this manual. See Appendix A, Table A-2.

For aluminum cables, wire brush the wire strands

thoroughly. Immediately after wire brushing, coat the

cable strands with a quality oxide inhibiting compound

such as Penetrox A. Insert exposed wires into the

terminals and tighten the set screws in accordance with

values shown in the torque Table A-2 in Appendix A of

this Instruction Book.

CAUTION: The torque values shown in the table are

for dry threads only. Do not grease or otherwise

lubricate the threads on the cable terminals, as this

will permit over-tightening of the screw and possible

damage to the terminal or cable.

ATTENTION: Les valeurs de couple indiquées dans le

tableau ne sont valables que pour des filets secs

uniquement. Il ne faut pas graisser ou librifier

autrement les filets des câbles terminaux, car cela

produira un serrage excessif de la vis et possiblement

des dommages au terminal ou au câble.

This should result in the oozing of compound material

from between individual strands. Wipe off any excess

compound.

Bolt the cable terminal connectors to the ends of the bars

in the cable compartment. Non-oxidizing grease, such as

GE lubricating grease D6A15A2 furnished with each

lineup, should be used at these connection surfaces. The

bolts should be tightened with a torque of 35-40 ft-lbs.

Lash the cables securely to the cable support, if present, to

take their weight off the runbacks and to brace them

against short circuit forces in the event of a fault.