Entellisys Low Voltage Switchgear

Chapter 3. Description

1. Racking arm

2. Drawout interlock


Fig. 3-8. EGX-08 circuit breaker

EntelliGuard breakers do not contain current transformers.

Instead, current transformers are mounted over the primary

disconnect stabs of all Entellisys breaker compartments.

Primary disconnects are equipped with short-circuit braces

when breakers are fused or when extra-deep breaker

compartments are used.

The breaker racking arm slots engage fixed racking anchor

pins (6), Fig. 3-6, mounted in the breaker compartment. As

the racking arms are rotated by operation of the breaker

racking crank, the breaker is pulled into the compartment,

and locked in its final connected position.

A breaker should always be OPEN when it is moved into or

out of the CONNECTED position. As a safeguard, the

drawout interlock (2), Fig. 3-8, will cause the breaker to open

before the primary disconnects lose contact if a closed

breaker is moved out of the CONNECTED position.

EntelliGuard circuit breakers having higher continuous or

interrupting current ratings may be substituted for those

having lesser ratings. The compartment, however, retains the

factory-configured ratings and protection settings.

Substitution of manual for electric or electric for manual

EntelliGuard breakers is not recommended.



1. Racking arm

2. Secondary disconnects

3. Racking screw

Fig. 3-9. EGS-40 circuit breaker

Each breaker compartment has four positions as described

below:

1.

CONNECTED POSITION-The breaker is in operating

position, both primary and secondary contacts made,

and the door closed.


2.

TEST POSITION-The secondary contacts are made, but

the primary contacts are not made. Any breaker test

that requires control power may be made in this

position.


3.

DISCONNECTED POSITION-All primary power and

secondary control electrical circuits between the breaker

and the equipment are disconnected. The door may be

closed. The breaker may be stored in this position with

the door closed.


4.

WITHDRAWN POSITION-The breaker is completely

out of its compartment ready for removal from the

equipment. The door must be open. The optional

primary disconnect shutters, positioned in front of the

primary stabs, would be closed with the breaker in the

WITHDRAWN position.