Entellisys Low Voltage Switchgear

Chapter 5. Installing and Removing Circuit Breakers

5-3 Installing EG-32/40/50 Circuit
Breakers

WARNING: Do not stand under the circuit breaker

during the hoisting operation.

ADVERTISSEMENT: Il est interdit de se tenir sous le

disjoncteur durant l’opération de levage.

CAUTION: When using the switchgear hoist, do not un-

wind the cable completely from the drum. To lift the

breaker, turn the hoist operating crank clockwise. To lower

the breaker, turn the hoist operating crank counter-

clockwise.

ATTENTION: Il ne faut pas dérouler complètement le

câble du cylindre lorsque l’on utilisse le treuil du dispositif

de commutation. Tourner la manivelle opérant le treuil

dans le sens des aiguilles d’une montre pour soulever le

disjoncteur. Tourner la manivelle opérant le treuil dans le

sens contraire des aiguilles d’une montre pour abaisser le

disjoncteur.


Installation Procedure
To position the EGS-32/40/50 circuit breaker on the drawout

rails, proceed as follows:

1.

Carefully place the breaker in front of the section in

which it is to be installed, See fig. 5-4.


2.

Open the breaker compartment door by rotating the

door latch assembly ¼ turn clockwise.


3.

Using the switchgear hoist or a suitable lifting

mechanism and the appropriate spreader for EG-

32/40/50, raise the breaker above the elevation of the

rails. See Fig. 5-5.


4.

Pull the drawout rails all the way out to its WITH-

DRAWN limit. The rail pin will be positioned at the

back of the rail slot.


5.

Slowly lower and guide the breaker to allow the 4

breaker wheels to align with the rails. See Fig. 5-7.

Remove the lifting device. The breaker is now

positioned on the drawout rails.


6.

Roll the breaker into the compartment until the racking

cams touch the racking pin and the spring discharge

stop engages. This is the DISCONNECT position. At

this point, the racking cams are positioned to engage

the fixed racking pins in the compartment, ready to

begin the racking motion. If the incorrect breaker has

been installed, the interference pins on the breaker will

interfere with the rejection teeth in the compartment

prior to reaching the disconnect position (Fig. 5-10).



7.

Slide rails back into compartment. Close the

compartment door and rotate latch ¼ turn counter-

clockwise.


8.

With the EG-32/40/50 breakers rotate the racking

access cover in the door and engage the racking handle

9.

Rotate the handle clockwise as far as it will go. As you

rotate the handle clockwise, the breaker will travel from

the disconnect, through the test position (you will notice

an audible click as the secondary disconnects engage),

and then into the connect position. The breaker

position can be seen on the indicator, located on the

breaker escutcheon.

Fig. 5-10. Rating rejection bracket on EG-32/40/50


Fig. 5-11. Spring discharge interlock used on manually and electrically

operated breakers