GE Industrial Solutions Entellisys Installation User Manual

Page 50

Advertising
background image

44

Entellisys Low Voltage Switchgear

Chapter 5. Installing and Removing Circuit Breakers

CAUTION: When using the switchgear hoist, do not un-

wind the cable completely from the drum. To lift the

breaker, turn the hoist operating crank clockwise. To

lower the breaker, turn the hoist operating crank counter-

clockwise.

ATTENTION: Il ne faut pas dérouler complètement le

câble du cylindre lorsque l’on utilisse le treuil du dispositif

de commutation. Tourner la manivelle opérant le treuil

dans le sens des aiguilles d’une montre pour soulever le

disjoncteur. Tourner la manivelle opérant le treuil dans le

sens contraire des aiguilles d’une montre pour abaisser le

disjoncteur.

4.

Fully withdraw rails to stops.


5.

Slowly lower and guide the breaker to allow the 4

breaker wheels to align with the rails. See Fig. 5-7.

Remove the lifting device. The breaker is now

positioned on the drawout rails.


6.

Roll the breaker into the compartment until the racking

forks meet the racking pin, this is the DISCONNECT

position. If an incorrect breaker has been installed, the

interference pins on the breaker will interfere with the

rejection pins in the compartment prior to reaching the

DISCONNECT position. See Fig. 5-8. At this point, the

racking forks are contacting the fixed racking pins in

the compartment.


7.

Slide rails back into compartment. Close the com-

partment door and rotate latch ¼ turn counter-

clockwise.


8.

Engage the racking handle by pushing and holding the

trip button in the breaker escutcheon, sliding the cover

just below it to the right, releasing the trip button, and

inserting the handle on the jackshaft. See Fig. 5-9.


9.

Rotate the handle clockwise as far as it will go. As you

rotate the handle clockwise, the breaker will travel from

the DISCONNECT, through the TEST position (you will

notice an audible click), and then into the CONNECT

position. The breaker position can be seen on the

indicator, located on the breaker escutcheon.








Fig. 5-8. Push the breaker in completely. Close the door.

Fig. 5-9. Engage the racking screw with the racking handle

Advertising