Entellisys Low Voltage Switchgear

Chapter 7. Operating the Switchgear

7-4 Entellisys Switchgear
Accessories

Future Circuit Breaker Compartments

Breaker compartments designed for future use are complete

and ready to use. These breaker compartments have a steel

panel to cover the door cutout, Fig. 7-4. To prepare the

circuit breaker compartment for use, remove the steel outer

cover.

WARNING: Terminals behind the steel barrier may be

energized.

AVERTISSEMENT: Il se peut que les bornes à l’arrière

de la barrière d’acier soient sous haute tension.

Fig. 7-4. Future-use breaker compartments

Circuit Breaker Key Interlock

General

A circuit breaker key interlock is available to provide

protection against unauthorized operation. See Fig. 7-5.

The key interlock is mounted with two one-way screws and

lockwashers on the left side of the breaker compartment.

The interlock system is designed so that the key may be

removed from the lock only when the breaker is tripped and

the lock bolt is extended. With the bolt extended, the

breaker is rendered trip free only in the CONNECT position

in this compartment.

The breaker may be operated (open, trip, charge, close) in

the TEST position even when the lock bolt is extended and

the key removed.

Key Interlock Operation Check

The operation of the key interlock should be checked as

follows:

1.

With the breaker in the CONNECT position, manually

trip the breaker. This then allows the interlock trip

slide to be pushed in. When the trip slide is in, the lock

bolt may be extended and the key removed. The

breaker will remain trip free in the CONNECT position

until the key is returned and the lock bolt is retracted.

Fig. 7-5. View showing circuit breaker key interlock to provide

protection against unauthorized operation

2.

If desired, the breaker may be moved to either the

TEST position while the key is removed from the lock.

In these positions, the breaker can be operated for

checking or maintenance.

Test and Disconnect Padlock Device

General

WARNING: This padlock lockout does not provide

equipment de-energization, isolation and grounding

required for maintenance personnel safety. See

instruction book DEH-203 or DEH-204 for details.

AVERTISSEMENT: Le mécanisme de verrouillage à

cadenas ne fournit pas la mise hors tension adéquate de

l’équipement, l’isolation et las mise à la terre requis pour

assurer la sécurité du personnel de maintenance. Voir les

instructions DEH–203 ou DEH–204 pour les details.

A test and disconnect rackout mechanism padlock device is

available to prevent unauthorized racking of the breaker.

The rackout mechanism for circuit breakers and FRE may be

locked in either the DISCONNECT or TEST position.