4-1

Figure 4-1. REMOVING THE TOP COVER

Unit Cover (Middle)

Mounting Screw

Holes

Keypad Panel

Unit Cover (Top)

Top Cover Screw

Removing Top Cover

To access Main and Control Circuit Terminals remove the top
cover as follows (see Figure 4-1):

1. Loosen the screw located at the bottom of the top cover.

2. Press upward on the bottom of the top cover (see arrows

Figure 4-1 step 2) and lift off.

3. See Figure 4-1 for the location of the Main Circuit

Terminal Block and the Control Circuit Terminal Block.

Section 4
WIRING PROCEDURES

WARNING

:

Some printed circuit boards and Drive com-

ponents may contain hazardous voltage levels. If LED
light "CRG" on the Base Driver Board is illuminated,
hazardous voltages are present in the Drive circuit boards.
Remove and lock out power before you disconnect or
reconnect wires, and before you remove or replace fuses
and circuit boards. Do not attempt to service the Drive
until the "CRG" indicator has extinguished and the bus
voltage has discharged to zero volts.

Control
Circuit
Terminal
Block

Step 2:

Press Upward at the locations indi-
cated by the arrows to remove the top
cover.

Main Circuit
Teminal Block

Drive
Charge "CRG" Lamp

Heat Sink

and Mounting Tabs

Step 1:

Loosen Top Cover
screw. (1 to 2 turns)