GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 51

Advertising
background image

6-12

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

V

Contents of the

last trip are

displayed.

Contents of the

second-last trip

are displayed.

Contents of the

third-last trip

are displayed.

Contents of the

fourth-last trip

are displayed.

This example

shows there is no

trip history for this.

*F_29

PROTECTION HISTORY/FAULT MEMORY

– –

The Last 4 drive faults are displayed in order
when the key is pressed.

Operation Procedure

F_30

0 to 15

STARTING FREQUENCY

1 Hz

This sets the starting frequency within the range of 0 to
15Hz in 1Hz steps.
If the data is set to 0, the frequency will be 0.2Hz.

*F_31

TORQUE LIMIT

0

(During Acceleration/Deceleration)
Sets the Torque Limit level during acceleration/
deceleration in steps of 1%.

0

No limit

20

20%

to

Limit

180

180%

*F_32

TORQUE LIMIT

0

(At Constant Speed)
This sets the torque limit level during constant speed
operation in steps of 1%.

0

No limit

20

20%

to

Limit

180

180%

If the torque limit function has been selected, the Drive may
start running with differences in the acceleration/deceleration
time and speed settings. Make sure that the system is set up
properly so that there will be no danger to personnel when the
Drive starts, otherwise accidents may occur.