TROUBLESHOOTING

If the function of the Drive is lost by a failure or if an abnormal condition has occurred, refer to the following diagnosis
for its probable cause.

If the cause does not fall under the following explanation, or if the Drive is damaged, please contact GE Fuji Technical
Services for assistance.

( 1 ) Overcurrent

Overcurrent

Overcurrent

during

during

Overcurrent at

acceleration

deceleration

constant speed

No

No

O C 1

O C 2

O C 3

Is motor circuit (U,V, W) of motor shorted or grounded?

Is the load too large?

No

No

Repair
short-circuit
and/or
grounding.

Is the
deceleration
time setting
too short for
the load?

Is the torque
boost setting
correct?

Does the load
change
suddenly?

Can the
deceleration
time be
increased?

Increase the
setting time.

Yes

Yes

Yes

Increase the
setting time.

No

No

Is the
acceleration
time setting too
short for the
load?

Can the
acceleration
time be
increased?

Yes

Yes

Yes

Reduce the
load fluctua-
tion or use a
Drive with
higher
capacity.

Reduce the
load fluctua-
tion or use a
Drive with
higher
capacity.

Yes

No

No

Yes

No

No

Yes

Can the torque
boost setting
be reduced?

No

No

Reduce the
torque boost
setting

No

Review the system
application.
Contact GE Fuji
Electric.

There is a
possibility of
Drive failure
or a motor
noise problem.
Contact GE Fuji
Electric.

Reduce the
load
fluctuation
or use a Drive
with higher
capacity.

There is the
possibility of
failure in the
Drive or a
noise problem.
Contact GE
Fuji Electric

Advertising