GE Industrial Solutions AF-300 MICRO-$AVER II User Manual
Page 49
6-10
LED
Data
Factory
Customer
Display
Setting
Description
Setting
Setting
*F_21
MULTISTEP FREQUENCY #1
5.00Hz
*F_22
MULTISTEP FREQUENCY #2
10.00Hz
*F_23
MULTISTEP FREQUENCY #3
20.00Hz
*F_24
MULTISTEP FREQUENCY #4
30.00Hz
*F_25
MULTISTEP FREQUENCY #5
40.00Hz
*F_26
MULTISTEP FREQUENCY #6
50.00Hz
*F_27
MULTISTEP FREQUENCY #7
60.00Hz
These Functions set the frequency for multistep
frequency operation. The frequencies are selected as
shown in the table below by setting control terminals
X1-CM, X2-CM and X3-CM to ON/CLOSED.
[Relationship between terminals and multistep
frequencies 1-7]
•
= ON/CLOSED
(1) Speed 0 (when X1-CM, X2-CM and X3-CM are all
OFF/OPEN) depends on the frequency setting method
selected by means of function F_01. In other words, the
setting becomes digital (using the and keys) or
analog ([0 to 10VDC] or [4 to 20mA VDC]).
(2) The actual operation frequency is limited by the maximum
frequency F_03 and the frequency limiters F_36 and F_37.
Function
1
21
22
23
24
25
26
27
Multistep
Speed Speed Speed Speed Speed Speed Speed Speed
Frequency
0
1
2
3
4
5
6
7
X1 – CM
•
•
•
•
X2 – CM
•
•
•
•