*F_52
0.02 to 5.0
FREQUENCY SETTING SIGNAL FILTER
.06s
This Function Code is used to set the time constant
for the input filter in order to eliminate the effects of
noise present in the analog signals (voltage and current
references). If the time constant set point is too long,
the response to changes in analog commands
will become inadequate for the required performance
level. Adjustable from 0.02 to 5.00 seconds in 0.02
increments.
F_53
TIMER (AUTOMATIC RUN/STOP CYCLE)
0.00s
This sets the timer to active or inactive, and also sets
the time from the start of operation until operation
automatically stops (when the timer is active).
0:
Inactive (Normal Operation)
001 to
Active (0.01 second)
3600
Active (3,600 seconds)
Setting Range
Setting Step
Unit
0.00 to 9.99
0.01
10.0 to 99.9
0.1
second
100 to 999
1
(s)
1000 to 3600
10
RUN LED
Lit
To restart the cycle, the closed FWD(REV)-CM has to
be opened and then re-closed. F_02 = 1.
When FWD (REV)-CM is opened during timer operation,
the timer is cleared.
When power failure occurs during timer operation, the
timer is cleared.