GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 59

Advertising
background image

6-20

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

FDT
HYSTERESIS

FDT
HYSTERESIS

FAR
SIGNAL OFF ON ON OFF

OFF

*F_56

0 to 30

HYSTERESIS WIDTH

0 Hz

This sets the hysteresis for the frequency detection signal
(FDT) and frequency equivalence signal (FAR) within the
range of 0-30 Hz.
The FAR is in the middle of the hysteresis width. F_54 = 2

(Y1-CM)

FAR

F_57

THR TERMINAL

0

(Function Selection)
This sets the function for the THR input terminal.

0:

Used for THR functions (Trip Command Functions)

1:

Used for Edit Permit Commands
THR-CM off: Function data change not possible.
THR-CM on: Function data change possible.

The relationship between this function and function F_00
(Data protection) is shown in the table below:

F_57

F_00

Data changing

Edit permit command

Data protection

possible

0 (OFF)

0

No

0 (OFF)

1

No

1 (ON)

0

Yes

1 (ON)

1

No

Advertising