Function code descriptions (01 thru 79), Settings and diagrams), Basic functions – GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 40

Advertising
background image

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

6-1

F_00

DATA PROTECTION

0

This Function protects the data setting from
accidental changes.

0

Data Changeable

1

Data Protected

To change the Data Protection Setting,
simultaneously press the
key and either the or key.

F_01

FREQUENCY COMMAND

0/1*

The frequency reference setting method can be selected.

0

Using the Keypad Panel and keys

1

Using analog signal input
Note: The frequency setting will be the sum of the
values at terminal 12 (0 to 10 VDC) and terminal C1
(4 to 20mA dc).

2

UP/DOWN Control
Output frequency can be increased or decreased by signal
input to the terminals X1 and X2.
The adjustable range is from minimum frequency to max
frequency. If the terminals X1-CM is held closed, output
frequency increases by F63 (2nd acceleration time). When
the terminals X2-CM is held closed, output frequency
decreases by F64 (2nd deceleration time). The rotation
direction can not be changed. The rotation direction
depends on input to the terminal FWD or REV.

NOTE: * =

Function can be changed while Drive is operating.

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

Basic Functions

Section 6
FUNCTION CODE DESCRIPTIONS

STOP

*Default value = 0
Factory setting for NEMA1 = 1. Will reset to 0 when default is selected

Advertising