GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 42

Advertising
background image

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

6-3

F_02

OPERATION COMMAND

0/1*

Selection of the input method for operation commands

0

Operation command input using the keypad
(RUN and STOP keys)

1

Operation command input by means of the
external signal terminal (FWD, REV). STOP key on
the keypad is active.

2

Operation command input by means of the
external signal terminal (FWD, REV). STOP key on
the keypad is inactive.

If selection "1" is chosen, and the stop button is depressed
while the drive is running, the drive will perform the
normal stop sequence until when the output frequency
reaches zero at which point an "Er6" fault shall be
indicated on the LED.

NOTE: To change the Operation Command Setting
the following three conditions must be met:
1. Remove jumper between CM to FWD
2. Open between CM to FWD and CM to REV
3. F_43 = 3 for Three Wire Control cannot be selected.

F_03

MAXIMUM FREQUENCY

60

50

Maximum operating frequency can be set within

to

the range of 50 to 400 Hz in steps of 1 Hz.

400

F_04

15

BASE FREQUENCY 1

60

to
400

The range is 15 to 400 Hz in steps of 1 Hz.
Normally set to the rated nameplate frequency
of the motor.

NOTE: If the Base Frequency is greater than the
Maximum Frequency, the output voltage will not
rise to the rated voltage. Set so that the ratio
between the Base Frequency and the Maximum
Frequency is less than 1:8.

*Default Value = 0
Factory Setting for NEMA 1 = 1
Setting will reset to 0 when default is
selected

WARNING: Prior to operating a motor above its base
frequency, you must review the operational capabilities
of the motor. Failure to do so could result in severe
damage to the motor and could result in injury to
personnel.