GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 55

Advertising
background image

6-16

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

F_40

FMA, FMP TERMINALS

0

(Operation Selection)
This switches the output destination for the external
monitoring signal.

0:

Analog signals are output from the FMA terminal.
(The FMP terminal cannot be used.)
The type of analog signal output to the FMA terminal is
selected by function F_41.

1:

Pulse signals are output from the FMP terminal.
(The FMA terminal cannot be used.)
Frequency of pulse signal output to the FMP terminal is
adjusted by function F_42.

F_41

FMA TERMINAL

0

(Function selection)
This sets the type of analog signal which is output
to the FMA terminal.

0:

Output frequency: 0 to 100% full scale

1:

Output current: 0 to 200% full scale

2:

Output torque: 0 to 200% full scale

3:

Output power: 0 to 200% full scale

*F_42

1 to 100

FMP TERMINAL

24

(Pulse Rate Multiplier)
This sets the pulse rate multiplier for the pulse signal
frequency output to the FMP terminal with respect to
the Drive output frequency. The setting range is
1 to 100.

FMP terminal pulse frequency = Drive output frequency X [Pulse rate multiplier]