480v – three phase – GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 23

Advertising
background image

4-4

Table 4:

Wire Size Recommendations

& Circuit Protection Ratings

240V – Single Phase and 230V Three Phase

DB Incoming

Power

Model

PH

HP

Output Current

Power

Resistor**

AC – Line Devices

NEMA 1

NEMA 4

Const

Carrier Frequency

Wire Wire

Circuit

Input

TRQ

Low

High

AWG

AWG

Fuses*

Breaker

6KM$221F25N1A1 6KM$221F25X4A1

1

1/4

1.5

1.3

16

-

6

5

6KM$221F50N1A1 6KM$221F50X4A1

1

1/2

3

2.5

16

16

10

10

6KM$221001N1A1 6KM$221001X4A1

1

1

5

4

14

14

15

15

6KM$221002N1A1 6KM$221002X4A1

1

2

8

7

12

12

20

20

6KM$221003N1A1 6KM$221003X4A1

1

3

11

10

10

10

30

30

6KM$223F25N1A1 6KM$223F25X4A1

3

1/4

1.5

1.3

16

-

6

5

6KM$223F50N1A1 6KM$223F50X4A1

3

1/2

3

2.5

16

16

10

5

6KM$223001N1A1 6KM$223001X4A1

3

1

5

4

16

16

15

10

6KM$223002N1A1 6KM$223002X4A1

3

2

8

7

14

14

20

15

6KM$223003N1A1 6KM$223003X4A1

3

3

11

10

14

14

30

20

6KM$223005N1A1 6KM$223005X4A1

3

5

17

16.5

10

10

40

30

480V – Three Phase

DB Incoming

Power

Model

PH

HP

Output Current

Power

Resistor**

AC – Line Devices

NEMA 1

NEMA 4

Const

Carrier Frequency

Wire Wire

Circuit

Input

TRQ

Low

High

AWG

AWG

Fuses*

Breaker

6KM$243F50N1A1 6KM$243F50X4A1

3

1/2

1.6

1.4

16

14

6

5

6KM$243001N1A1 6KM$243001X4A1

3

1

2.5

2.1

16

14

6

5

6KM$243002N1A1 6KM$243002X4A1

3

2

3.7

3.7

16

14

15

10

6KM$243003N1A1 6KM$243003X4A1

3

3

5.5

5.3

16

14

15

15

6KM$243005N1A1 6KM$243005X4A1

3

5

9.0

8.7

14

14

20

15

WARNING - Device ratings such as system coordination, short-circuit
rating and type must be carefully reviewed by the user
.

NOTE:

Wire size from NEC table 310-16. Copper wire rated 60

°

C for 100 amps or less,

75

°

C for over 100 amps in 30

°

C ambient and 1.25 times Drive rated amps. These

are minimum wire sizes; consult and conform to local and national codes.

* NOTE: AC input fuses are required to validate the drive's UL and CSA approvals.

The fuse should be Class J type such as Bussman, JKS or equivalent. Circuit breaker
ratings are shown for reference, but UL and CSA approval can only be validated by
the use of Class J fuses.

** Optional Item.