LED
Data
Factory
Customer
Display
Setting
Description
Setting
Setting
6-9
F_17
DC BRAKE (Operation Selection)
This selects the DC brake operation to active or inactive
0
0:
Inactive - (Regenerative braking only)
1:
Active - (DC braking after regenerative braking)
*F_18
0 to 60
DC BRAKE (Starting Frequency)
Sets the frequency to start DC injection brake
0 Hz
operation during deceleration.
*F_19
0 to 100
DC BRAKE (Brake Level)
Sets the output braking level (brake output) for the DC
50%
injection brake. The braking strength will
vary depending on the characteristics of the motor.
*F_20
0.00 to 30
DC BRAKE (Braking Time)
Sets the operation time for the DC injection brake.
0.5s
1
If the data is set to "0", the frequency will be 0.2 Hz.
The Drive braking function cannot be substituted
for mechanical means. Attempting to do so may
result in injury.
Starting Range
Unit
Setting Step
Starting Frequency
0
1
to 60
Hz
1 Hz
Braking Level
0 to 100
%
1%
Braking Time
s
0.00 to 9.99
10.0 to 30.0
0.01
0.1
Operating
Speed
Operating
Speed
Time
→
Time
→