GE Industrial Solutions AF-300 MICRO-$AVER II User Manual
Page 62
LED
Data
Factory
Customer
Display
Setting
Description
Setting
Setting
6-23
F_69
TORQUE VECTOR CONTROL
0
This selects whether Torque Vector Control is active
or not.
0:
Torque Vector Control inactive
1:
Torque Vector Control active
NOTE: Torque Vector Control does not function if
is selected when the X4 terminal function has been set
to (F_43 = 2) and X4-CM is ON/CLOSED. The manual
torque boost selected by F_65 will apply.
NOTE: For best results perform Auto Tuning Function
(F_74) prior to activation of Torque Vector Control.
F_70
MOTOR HP CAPACITY
1
This sets the HP capacity of the motor which is connected
in relation to the Drive capacity.
0:
1-frame up capacity for standard applied motor
1:
Standard capacity for standard applied motor
2:
1-frame down capacity for standard applied motor
3:
2-frame down capacity for standard applied motor
F_71
0.00
MOTOR 1 RATED CURRENT
4-pole
F_72
to
MOTOR 1 NO-LOAD CURRENT
4-pole
99.9
These set the rated current (A) and no-load current (A)
(Std.
for the motor which is connected to the Drive.
Design B)
EXPLANATION: The primary resistance (R
1
) and
leakage reactance (X
1
) are automatically rewritten
with the rated value of the motor capacity (F_70),
motor 1rated current F_71 and motor 1no-load
current (F_72) are set.
F_73
0.00
MOTOR 2 RATED CURRENT
Rated
to
This sets the rated current (A) for the second motor which
Current
99.9
is selected when base frequency 2 (F_62) is active.
(Std. 4-Pole
Motor)