GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 62

Advertising
background image

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

6-23

F_69

TORQUE VECTOR CONTROL

0

This selects whether Torque Vector Control is active
or not.

0:

Torque Vector Control inactive

1:

Torque Vector Control active

NOTE: Torque Vector Control does not function if
is selected when the X4 terminal function has been set
to (F_43 = 2) and X4-CM is ON/CLOSED. The manual
torque boost selected by F_65 will apply.
NOTE: For best results perform Auto Tuning Function
(F_74) prior to activation of Torque Vector Control.

F_70

MOTOR HP CAPACITY

1

This sets the HP capacity of the motor which is connected
in relation to the Drive capacity.

0:

1-frame up capacity for standard applied motor

1:

Standard capacity for standard applied motor

2:

1-frame down capacity for standard applied motor

3:

2-frame down capacity for standard applied motor

F_71

0.00

MOTOR 1 RATED CURRENT

4-pole

F_72

to

MOTOR 1 NO-LOAD CURRENT

4-pole

99.9

These set the rated current (A) and no-load current (A)

(Std.

for the motor which is connected to the Drive.

Design B)

EXPLANATION: The primary resistance (R

1

) and

leakage reactance (X

1

) are automatically rewritten

with the rated value of the motor capacity (F_70),
motor 1rated current F_71 and motor 1no-load
current (F_72) are set.

F_73

0.00

MOTOR 2 RATED CURRENT

Rated

to

This sets the rated current (A) for the second motor which

Current

99.9

is selected when base frequency 2 (F_62) is active.

(Std. 4-Pole

Motor)