GE Industrial Solutions AF-300 MICRO-$AVER II User Manual
Page 53
6-14
LED
Data
Factory
Customer
Display
Setting
Description
Setting
Setting
*F_35
0.00
GAIN FOR FREQUENCY SETTING SIGNAL
100.0%
to
This sets the size (gradient) of the output frequency
250
corresponding to the analog frequency setting as a
percentage of the maximum frequency.
[Example: for 70% gain] [Example for 200% gain]
*The gain setting is only active when F_01 = 1
Example:
If the bias frequency function (F_34) and the gain for
frequency setting signal function (F_35) are used together,
the gain for frequency setting signal has priority, and the
bias is applied to the frequency with gain already applied.
The bias frequency f
bias
and setting frequency gain at
this time can be calculated by the following formulas.
f
1
– f
2
f
bias
= f
1
– x V
1
V
1 –
V
2
1000 x (f
1
– f
2
)
Gain =
100 x (V
1
– V
2
) + f
1
x V
2
– f
2
x V
1
Example:
If the analog frequency setting voltage is 1 to 5Vdc
and the output frequency is weighted to 0 to 100% then:
(V
1
, f
1
) = ( 1, 0) , (V2, f2) = ( 5,100), so that
[V] [%] [V] [%]
f
bias
= –25% and gain = 200%