GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 53

Advertising
background image

6-14

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

*F_35

0.00

GAIN FOR FREQUENCY SETTING SIGNAL

100.0%

to

This sets the size (gradient) of the output frequency

250

corresponding to the analog frequency setting as a
percentage of the maximum frequency.

[Example: for 70% gain] [Example for 200% gain]
*The gain setting is only active when F_01 = 1

Example:
If the bias frequency function (F_34) and the gain for
frequency setting signal function (F_35) are used together,
the gain for frequency setting signal has priority, and the
bias is applied to the frequency with gain already applied.
The bias frequency f

bias

and setting frequency gain at

this time can be calculated by the following formulas.

f

1

– f

2

f

bias

= f

1

– x V

1

V

1 –

V

2

1000 x (f

1

– f

2

)

Gain =

100 x (V

1

– V

2

) + f

1

x V

2

– f

2

x V

1

Example:
If the analog frequency setting voltage is 1 to 5Vdc
and the output frequency is weighted to 0 to 100% then:

(V

1

, f

1

) = ( 1, 0) , (V2, f2) = ( 5,100), so that

[V] [%] [V] [%]

f

bias

= –25% and gain = 200%

Advertising