INSPECTION ITEMS CHART
Item
Inspection Criteria
Corrective Action
Power Supply
Within permissible limits (170-264 Vac)
Adjust the power supply voltage.
Voltage
for 1 Phase 240 VAC Drives; (170-253)
for 3 Phase 230 VAC Drives; and
(323-528) for 3 Phase 480 Vac Drives.
Ambient
Within permissible limits (-10
°
to +50
°
C)
Investigate cause and make corrections
Temperature
(+14
°
to +122
°
F.)
until environment is within permissible limits.
Ambient
Within permissible limits (20 - 95% RH)
Investigate cause and make corrections
Humidity
No dew condensation or freezing.
until environment is within permissible limits.
Vibration
Within permissible limit (0.6G or less)
Investigate cause and make adjustments.
until within permissible limits.
Noise
Abnormal audio noise from cooling
Contact the supplier where the Drive
fan, etc.
was purchased.
Odor
Smell or burning.
Contact the supplier where the Drive
was purchased.
Dust
Dust accumulation on cooling fins,
Clean and blow out with dry and filtered
cooling fan, or on the control board.
compressed air.
Screws/
Check for any loosening.
Re-tighten as needed.
Connectors
INSPECTION ITEMS
Refer to the Inspection Items Chart in this section for inspection points and corrective action.