7-2

INSPECTION ITEMS CHART

Item

Inspection Criteria

Corrective Action

Power Supply

Within permissible limits (170-264 Vac)

Adjust the power supply voltage.

Voltage

for 1 Phase 240 VAC Drives; (170-253)
for 3 Phase 230 VAC Drives; and
(323-528) for 3 Phase 480 Vac Drives.

Ambient

Within permissible limits (-10

°

to +50

°

C)

Investigate cause and make corrections

Temperature

(+14

°

to +122

°

F.)

until environment is within permissible limits.

Ambient

Within permissible limits (20 - 95% RH)

Investigate cause and make corrections

Humidity

No dew condensation or freezing.

until environment is within permissible limits.

Vibration

Within permissible limit (0.6G or less)

Investigate cause and make adjustments.

until within permissible limits.

Noise

Abnormal audio noise from cooling

Contact the supplier where the Drive

fan, etc.

was purchased.

Odor

Smell or burning.

Contact the supplier where the Drive
was purchased.

Dust

Dust accumulation on cooling fins,

Clean and blow out with dry and filtered

cooling fan, or on the control board.

compressed air.

Screws/

Check for any loosening.

Re-tighten as needed.

Connectors

INSPECTION ITEMS

Refer to the Inspection Items Chart in this section for inspection points and corrective action.