4 ) drive overheated, 5 ) external alarm input – GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 72

Advertising
background image

8-5

( 4 ) Drive overheated

O H 1

Is the Drive load
too large?

No

Yes

No

No

Reduce the load or
use a Drive with
higher capacity.

Replace the cooling
fan.

No

Yes

Remove
obstructions.

Yes

Yes

Is the cooling fan
in the Drive operat-
ing? (Above 2 HP)

Is the movement of
the Drive cooling
air obstructed?

Is the ambient
temperature within
the specified limit?

Possible Drive
failure or malfunc-
tion due to electrical
noise. Contact GE
Fuji Electric

Bring the ambient
condition to within
the specified limit.

( 5 ) External alarm input

Eliminate the cause of
the alarm.

Is the alarm function
of externally
connected equip-
ment activating?

Is the connection
between THR and
CM correct?

O H 2

Yes

Yes

Repair the wiring
and/or connections.

No

No

No

Connect
correctly.

Yes

Terminal C1–CM or
12-11 connected in
reverse.

– Drive Overheating
– Drive Overload

Possible Drive
failure or malfunc-
tion to electrical
noise. Contact GE
Fuji Electric