Table 5: terminal identification/function – GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 26

Advertising
background image

4-7

TABLE 5: Terminal Identification/Function

Terminal

Terminal

Label

Name

Function

POWER TERMINAL BOARD

L1, L2,

AC Supply Line

Connection for 200-230 VAC or 380-480 VAC, 3-phase, 50/60 Hz;

L3

Input Terminals

L1 & L2 for single phase input, 200-240 VAC 50/60 Hz

U, V, W

Drive Output

Connection for 3-phase induction motor

Terminals

P+, DB

External Braking

Connection for external braking resistor option for single phase and

Resistor Terminals

three phase drives (Only on 1⁄2 HP to 5 HP; not on 1/4 HP)

P1, P+

DC Reactor Terminals Connection for external DC reactor for power factor improvement

(Option). (Remove factory installed jumper)

CONTROL TERMINAL BOARD

11

Frequency Setting &

Common connector for terminals 12, 13, C1 and FMA (Do not

Analog Freq. Meter

connect to CM terminal or electrical noise immunity may be lost).

Common Terminal

12

Frequency Setting

When 0 to +10 VDC (0 to 5V*) is applied, the maximum frequency is

Voltage Input

reached at +10 VDC (5V*) and is proportional to output frequency
down to 0 VDC. Input impedance is 22K ohm ( *250% gain setting F_35)

13

Frequency Setting

Regulated +10 VDC power supply for frequency setting potentiometer,

Voltage Output Term.

10mA or less (13 to terminal 11)

C1

Frequency Setting

When the input signal is +4 to +20mA dc, the maximum frequency is

Current Input (+)

reached at 20mA and is proportional down to a minimum frequency
setting at 4mA. Input impedance is 250 ohm, must be isolated source

CM

Control Circuit

Common terminal for control input commands, X1-X4, FWD, REV, BX,

Common Terminal

RST, THR, Y1 and FMP pulse output signal
(Do not connect to terminal 11)

FWD

Forward Command
Input Terminal

Forward command via FWD-CM (closed). Reverse command via
REV-CM (closed). When FWD-CM and REV-CM are closed

Reverse Command

at the same time, the Drive will decelerate to stop

REV

Input Terminal

BX

Motor Coast-To-Stop

Motor will coast-to-stop with BX-CM (closed). (For use when

Command Input

applying mechanical brake with Drive in operation.) Note: If BX-CM is

Terminal

opened with FWD or REV closed, the Drive will start the motor

RST

Fault Reset Input

After removal of fault condition, Faults are reset when a momentary

Terminal

contact closure is made between the RST-CM terminals for more
than 0.1 seconds
If there is an input to the FWD or REV terminals with F_02 = 1 OR
2 and F_14 = 4 or 5 the Drive will suddenly restart.