GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 64

Advertising
background image

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

6-25

F_76

0.00 to 50

MOTOR 1 (%X Setting)

Std. 4-pole

This function displays the leakage reactance X1 of the

motor

motor in terms of percentage, and is set manually

The data can be overwritten and changed automatically
by automatic tuning using function F_74, or by setting
the motor capacity, rated current and no-load current
using functions F_70 to F_72.

Calculation Formula for %X1

X1 + X2 = Xm/ (X2 + Xm) + cable X

%X1 = x 100 [%]

V

/ (

3 •

I)

X1: Primary inductance of motor 1[Ohm]
X2: Secondary inductance of motor 1 [Ohm]
Xm

:

Mutual inductance of motor 1 [Ohm]

Cable X: [Ohm]
V: Rated voltage of motor

I

: Rated current of motor

: Value calculated for Y connection

%R1 and %X1 should be set to values which are appropriate
for the motor being used. The motor may not operate
correctly if these values are not set correctly, which could
result in accidents.

*F_77

000 to 999

TORQUE LIMITING RESPONSE
(At Constant Speed)

369

*F_78

000 to 999

TORQUE LIMITING RESPONSE
(During Acceleration/Deceleration

394

P – Represented by the Hundreds Digit (Gain Value)
I – Represented by the Tens and Units Digit (Time Constant)

F_79

OPTION SELECTION

0

This function sets whether an option is being used or
not, and also what type of option is being used if any.

0:

No Options

1:

DI option card used

2:

DI/O option card used

3:

RS option card used
NOTE: For details on setting specifications when

using an option card, refer to the instruction
manual which is supplied with the option card.

0 0 0

9 9 9

to

P I

P I

(Quick)

(Slow)

0 0 · · · 9 9

P

I

0 (Low)

·

·

9 (High)