S-CURVE ACCELERATION/DECELERATION

0

(Operation Selection)
Selects whether S-curve acceleration/deceleration
is active or inactive and which of the two S-curve
patterns is used.

0:

Inactive - linear acceleration and deceleration

(Fig. 1)

1:

S-curve acceleration/deceleration (weak) Fig.2

2:

S-curve acceleration/deceleration (strong) Fig. 3

NOTE:

Shocks at the start and end of acceleration and

deceleration can be softened by selecting a S-curve
pattern.

The maximum gradient in the output frequency

when a S-curve pattern is selected is the same as
for linear acceleration and deceleration time.

The actual acceleration and deceleration times when

a S-curve pattern is selected is extended by 10%
(when 1 is set) or 20% (when 2 is set) from the times
set by F_06 and F_07 or by F_63* and F_64*.

*

Alternate acceleration (F_63) and deceleration (F_64)

times are selected when the terminal X4 function is set so

that F_43 = 0 and X4-CM is ON/CLOSED.