GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 61

Advertising
background image

6-22

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

*F_65

1

TORQUE BOOST 2

13

2

This sets the torque boost 2 to one of 31 patterns when

3

terminal X4 has been set to function as a command input

to

terminal for switching to base frequency 2 (F_43 = 2).

31

Setting details are the same as for function F_08.

NOTE: For manual torque boost only; no pattern can be
selected for automatic torque boost.

F_66

See F_15

ELECTRONIC OVERLOAD 2

0

(Operation Selection)

F_67

See F_16

ELECTRONIC OVERLOAD 2

Rated motor

Current

(Operation Level)

(Std. 4

When terminal X4 has been set to function as a

Pole

command input terminal for switching to base frequency 2

Motor)

(F_43 = 2), this sets the electronic overload
to 2 (motor overload detection) for the second motor
to active or inactive, and also sets the operation pattern
and the operation level.
Setting details are the same as for function F_15 and F_16.

NOTE: Base frequency 2, torque boost 2 and electronic
overload 2 are only active when the X4
terminal function has been set to F_43 = 2 and
X4-CM is ON/CLOSED.

*F_68

0.0 to 5.0

SLIP COMPENSATION

0.0 Hz

Functions to suppress fluctuations in the motor speed
which result from variations in the load torque.
The slip frequency with respect to the base frequency
during rated load output (100%) can be set within the
range of 0.0 to 5.0 Hz in steps of 0.1 Hz.
If the slip compensation value is set to 0.0 Hz, then the
slip compensation function will be inactive.