GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 27

Advertising
background image

4-8

CONTROL TERMINAL BOARD (Continued)

THR

External thermal trip

With THR-CM (open), OH trip will occur and the motor will

command

coast-to-stop.
NOTE:

With no external thermal relay or external braking resistor

thermostat, the THR-CM terminals must be closed or the Drive
will not operate. THR-CM is factory pre-jumpered, remove prior to
connecting an external NC contacts.

FMA*

Analog Frequency

Provides an output of 0 to +10 VDC (+10VDC at max frequency),

Meter Connection

available for connection of a voltmeter with internal resistance of

F_40=0

10K ohms. See Function Code 41 for monitoring selection. Meter
connects between terminal FMA & 11. Note:

FMP cannot be used

FMP*

Digital Frequency

Pulse frequency output equal to Drive output frequency.

Meter Connection

Pulse voltage: Peak 5 VDC, 50% duty, Adjustable range = 600 to

F_40=1

6000 Hz (Max) See Function Code 42 Pulse Rate Multiplier.
Meter connects between FMP and CM. Note:

FMA cannot be used

30A

Fault Relay Output

During normal operation, the relay is not energized and contact is made

30B

Terminals

between 30B and 30C. When a fault is detected, the relay is energized

30C

and contact is made between 30A and 30C. (Contact rating resistive
load: 250 VAC, 0.3 Amps)

X1-X3

Multistep Frequency

Seven individual preset frequency selections via binary combination

Input Function

(closure) between X1, X2, X3, and CM.

Selection

Frequency selections determined using functions F_21 thru F_27.

X4

Function Extension

F_43=0 acceleration/deceleration time #2 is selected when X4-CM is

(Input)

closed. When not closed #1 setting is activated.
(F_43=1) 8 additional frequencies can be selected by X1, X2, X3 and X4.
(F_43=2) 2nd Motor selection when X4 - CM is closed.
(F_43=3) Functions as hold signal if 3-wire operation is desired.

Y1

Output Function

Outputs one of the following signals depending on setting of F_54;

(Programmable)

0: Drive running (RUN) 3: Undervoltage stop mode (LV)
1: Frequency level detection (FDT) 4: Torque limiting mode (TL)
2: Frequency equivalence (FAR) 5: Auto restart mode after

momentary power loss (IP)

Allowable load: Maximum 27VDC, 50mA or less

PLC

PLC

Prevents PLC fault caused by leakage current from the drive. (See Drive
interface details, Figure 4-7)

* Either an analog (FMA) or digital (FMP) frequency meter, not both.

TABLE 5: Terminal Identification/Function (continued)

Terminal

Terminal

Label

Name

Function

Advertising