LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

6-13

F_33

BRAKING TORQUE SELECTION

0

This sets the limit level for braking torque in accordance
with the brake being used.

0

Low (no Dynamic Braking option)

1

High (with Dynamic Braking option)
NOTE: Always connect an extra braking resistor. Contact

GE Fuji Technical Services for proper brake
resistor option selection.

*F_34

-400

BIAS FREQUENCY

0

to

This function adds the bias frequency offset to the analog

+400

reference frequency to produce the output frequency.
The setting range is between -400 to +400Hz in
steps of 1Hz.

*The bias frequency is only active when the frequency
setting function F_01 = 1

If the bias frequency has been set, the Drive will operate
when an operation command is given, even if the analog
frequency is zero.