GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 54

Advertising
background image

LED

Data

Factory

Customer

Display

Setting

Description

Setting

Setting

6-15

*F_36

0 to 400

HIGH FREQUENCY LIMITER

70 Hz

*F_37

0 to 400

LOW FREQUENCY LIMITER

0 Hz

The high and low limits for the output frequency can be
set within a range of 0 to 400Hz in stages of 1Hz.

NOTE:
If the high and low limit settings are reversed, the high
limit has priority and the low limit is ignored.

*F_38

0 to 10

MOTOR CHARACTERISTICS

5

This adjusts the output current in cases where there is
an irregularity such as current fluctuation. If a current
fluctuation occurs, adjust the setting value while
referring to the tables below.

F_39

DATA INITIALIZATION

0

This resets all Function Codes to factory settings.

0:

Inactive (manual setting)

1:

Initial values (Initialization with factory defaults)
[Operation Procedure]

When 0 is being displayed, press the STOP +

keys simultaneously to change the display to 1.

In this condition, press the key to reset

all data to the factory default settings. The display
will then automatically switch to show the frequency

setting for STOP mode.

Number of

Higher

4

Lower

Load

High

Low

Motor Poles

Setting

0

10

Setting

0

10

FUNC
DATA