*F_36
0 to 400
HIGH FREQUENCY LIMITER
70 Hz
*F_37
0 to 400
LOW FREQUENCY LIMITER
0 Hz
The high and low limits for the output frequency can be
set within a range of 0 to 400Hz in stages of 1Hz.
NOTE:
If the high and low limit settings are reversed, the high
limit has priority and the low limit is ignored.
*F_38
0 to 10
MOTOR CHARACTERISTICS
5
This adjusts the output current in cases where there is
an irregularity such as current fluctuation. If a current
fluctuation occurs, adjust the setting value while
referring to the tables below.
F_39
DATA INITIALIZATION
0
This resets all Function Codes to factory settings.
0:
Inactive (manual setting)
1:
Initial values (Initialization with factory defaults)
[Operation Procedure]
➀
When 0 is being displayed, press the STOP +
keys simultaneously to change the display to 1.
➁
In this condition, press the key to reset
all data to the factory default settings. The display
will then automatically switch to show the frequency
setting for STOP mode.